Megger 950 Torkel Battery Discharge Test Systems 220A 500V

$9360,00

New Megger 950 Torkel Battery Discharge Test Systems 220A 500V | Available EU-USA-AU-ASIA Stock for Low Tax & Free Shipping-Checkout Now

Description

Megger 950 Torkel Battery Load Unit

The Megger 950 Torkel of battery discharge test systems are Megger’s fourth generation of battery discharge analysers. Discharge testing is the only test method that provides a comprehensive insight into battery capacity, and is therefore an essential part of vigorous battery maintenance programmes.

Tests with the TORKEL900 series can be conducted at constant current, constant power, constant resistance, or in accordance with a pre-selected load profile. What’s more, if you connect the BVM battery voltage monitor to a TORKEL900 unit, the TORKEL becomes a complete standalone discharge test system.

Standard Package :
Megger TORKEL 950 Battery Load Unit Tester
Standard Transport Case
Mains Cable
2x 3m, 70mm² Cable Set
Soft Case for Cables
TORKEL Viewer
USB Memory Stick

Megger 950 Torkel CE-marking
LVD: IEC61010-1:2010 & IEC61010-2-030
EMC: IEC61326-1

General
Mains voltage: 100 – 240 V AC, 50/60 Hz
Power consumption: 200 W (max)
Power interruption: 40 ms (max)
Protection: Thermal cut-outs, Automatic overload protection, Emergency stop button
Dimensions: 519x315x375 mm, (20.5”x12.4”x14.7”)
Weight: 19.5 kg (43.0 lbs) instrument; 31.9 kg (70.3 lbs) incl. standard transport case; 37 kg (82 lbs) incl. large transport case
Display: 7″ LCD, Capacitive touch screen
Available languages: English, French, German, Spanish, Swedish

Measurement – Current measurement
Display range: 0.0 to 2999.0 A
Basic inaccuracy: ±(0.5% of reading +0.1 A)
Resolution: 0.1 A

Internal current measurement – Range: 0 to 220 A

Input for clamp-on probe
Range: 0 to 1000 mV DC
mV/A-ratio: 0.30 mV/A to 100.00 mV/A
Input impedance: >1 MΩ

Voltage measurement
Voltage: 0 to 500 V DC
Inaccuracy: ±(0.5% of reading +0.1 V DC)
Resolution: 0.1 V
Sample rate: 10 Hz, Values are saved when change is >10mV

Time measurement – Inaccuracy: ±0.1% of reading ±1 digit

Load
Battery voltage: 7.5 V to 300 V1)/500 V2)
Power: 15 kW (max)
Load patterns: Constant current, constant power, constant resistance, current or power profile

Constant I
Range: 0 to 220.0 A
Inaccuracy: ±(0.5% +0.2 A)
Resolution: 0.1 A
Ripple max: 0.5 A peak

Constant R
Range 300 mΩ to 3 kΩ
Inaccuracy ±1% typical
Resolution 100 mΩ

Constant P
Range: 0 to 15 kW
Inaccuracy: ±1% typical
Resolution: 10 W

Inputs
+: 7.5 to 300 V.1) 7.5 to 500 V.2)
–: 0 V
I EXT ≤ 1 V: 1 V DC, 300 V DC to ground
VOLTAGE SENSE: Impedance to the current terminals is >1 MΩ

Outputs

ALARM
Relay contact 28 V DC, 8 A, 240 V AC, 8 A
Devices higher than Cat II must not be attached

TXL STOP
Relay contact 250VDC, 0.28A, 28VDC, 8A, 250VAC, 8A
9 V DC 9 V DC, ±7% max 100 mA

Communication ports
BVM1 BVM2: USB connection for BVM units
USB: Connection for USB memory
Service port

Megger 950 Torkel Spec Datasheet User Manual PDF :

https://megger.com/en/products/torkel900-series-battery-discharge-test-systems

https://www.jpnpartsale.com/refund_returns/

Review :

Reviews

There are no reviews yet.

Be the first to review “Megger 950 Torkel Battery Discharge Test Systems 220A 500V”