SBS-1110S Battery Capacity Tester Load Bank 125 Vdc 0–100 Amp
$3244,00
Storage Battery System New SBS-1110S Ensure optimal battery performance with this reliable Capacity Tester 90–150Vdc 0–100A Available Stock.
Description
Storage Battery System SBS-1110S : Constant Current DC Load Bank 125 Vdc 0–100 Amp
The only way to know if your stationary batteries will perform to specification is to test them regularly.
NERC standard PRC-005-2 requires that vented lead acid and nickel cadmium (NiCd) systems be discharge tested every six (6) years and valve regulated lead acid (VRLA) batteries every three (3) years. IEEE recommends load testing stationary flooded/vented lead acid and NiCd stationary batteries every five (5 )years and VRLA batteries every 12–18 months.
The SBS-1110S constant current load banks are an easy and affordable way to perform accurate IEEE450 (Vented Lead-Acid), IEEE1106 (Ni-Cad) and IEEE1188 (VRLA) load tests.
These units are quick and easy to set up. They display the voltage, current and Ah removed from the string during the test. Since this is a constant current load bank, the user also does not have to adjust the current during the test.
These load banks come standard with multiple adjustable stop points and built-in protection to ensure that the batteries are never damaged due to over-discharge.
Features :
- 125V DC 0-100 Amp
- Automatically discharges batteries unmanned without danger of over-discharging
- Built-in protections: Over load protection, high voltage shutdown, high temperature shutdown, audible alarm, warning on LCD screen
- 3 adjustable stop points: End system voltage, Discharge time, Discharge capacity (Ah)
- User can set: end system voltage, test time, and capacity discharged
- Continuously holds the current set throughout the test
- LCD screen displays real time voltage, discharge current and capacity/Ah removed
- Test parameters adjustable during test: end system voltage, discharge time, discharge capacity (Ah)
- Units can be slaved with the SBS-8400 and/or other load banks to increase amp draw
- Perform IEEE450 (Vented Lead-Acid), IEEE1106 (Ni-Cad) and IEEE1188 (VRLA) load tests
Specification
| Weight | 44.000000 |
| Input | During discharge: real time voltage / current / test time / capacity discharged (Ah) User can set: end system voltage / test time / capacity discharged (Ah) |
| DC Cables | Included, 9 ft. long |
| DC Current Range | 0–100 A |
| DC Volt Range | 90–150 Vdc |
| Protection | Overheat / Overload / Over voltage protection with audible alarm and screen warning |
| Display Type | LCD (128 x 64 pixels) |
| Power Supply(s) | 1110S uses DC power supply (from tested battery) 125 and 250 Vdc units use AC power supply (110 Vac 60 Hz) |
| Test Type | Unit holds the set current throughout the test |
| Dimensions | 25 x 9 x 15 in. |