Megger TXL870 Extra Battery Load Unit

$4600,00

Megger TXL870 Extra Battery Load Unit For Torkel | Available EU-USA-AU-ASIA Stock for Low Tax and Free Shipping.

Description

Megger TXL870 Extra Battery Load Unit For Torkel.

The Megger TXL870 Extra Battery Load Unit is designed for use together with TORKEL battery testers. Their purpose is to provide higher load currents for use in constant current or constant power tests. Together, TORKEL and the TXL extra loads form a system that can discharge batteries with currents of up to several kA. TXL extra loads are connected directly to the battery, and TORKEL measures the total current using a clamp-on ammeter.

The Megger TXL870 extra load unit is shut down automatically when TORKEL is stopped.

There are five extra loads available: TXL830, TXL850, TXL865, TXL870, and TXL890. The details for these can be found in the TORKEL data sheet.

More Informations :
Megger TXL830, 850, 870, 890 Specifications
AC/DC Voltage
Voltage DC Max Current Max Power Max
TXL830 28 V 300 A 8.3 kW
TXL850 56 V 300 A 16.4 kW
TXL870 280 V 112 A 15.8 kW
TXL890 480 V 62 A 15.4 kW
Internal Resistance, 3-Position Selector
Position 1 Position 2 Position 3
TXL830 0.275 Ω 0.318 Ω 0.092 Ω
TXL850 0.55 Ω 0.275 Ω 0.184 Ω
TXL870 4.95 Ω 2.48 Ω 1.24 Ω
TXL890 14.10 Ω 7.05 Ω 3.52 Ω
Maximal Currents, 3 Position Selector
Position 1 Current Voltage Cells Cell Voltage
TXL830 100 A 27.6 V 12 2.3 V
78.5 A 21.6 V 12 1.8 V
TXL850 100 A 55.2 V 24 2.3 V
78.5 A 43.2 V 24 1.8 V
TXL870 50.1 A 248.4 V 108 2.3 V
39.2 A 194.4 V 108 1.8 V
TXL890 32.3 A 469.2 V 204 2.3 V
26.0 A 367.2 V 204 1.8 V
Position 2 Current Voltage Cells Cell Voltage
TXL830 200 A 27.6 V 12 2.3 V
156 A 21.6 V 12 1.8 V
TXL850 200 A 55.2 V 24 2.3 V
156 A 43.2 V 24 1.8 V
TXL870 50.1 A 124.2 V 54 2.3 V
39.2 A 97.2 V 54 1.8 V
TXL890 35.2 A 248.4 V 108 2.3 V
27.8 A 194.4 V 108 1.8 V
Position 3 Current Voltage Cells Cell Voltage
TXL830 300 A 27.6 V 12 2.3 V
235 A 21.6 V 12 1.8 V
TXL850 300 A 55.2 V 24 2.3 V
235 A 43.2 V 24 1.8 V
TXL870 100 A 124.2 V 54 2.3 V
74.8 A 97.2 V 54 1.8 V
TXL890 70.5 A 248.4 V 108 2.3 V
55.2 A 194.4 V 108 1.8 V
Environment The instrument is intended for use in high voltage substations and industrial environments.
Operating temperature 0°C to +40°C (32°F to +104°F).
Storage temperature -40°C to +70°C (-40°F to +158°F).
CE Marking LVD: IEC61010-1:2010
EMC: IEC61326 -1.
Main Voltage 100 – 240 V AC, 50 / 60 Hz.
Power consumption 75 W (max).
Protection Thermal cut-outs, automatic overload protection.
Dimensions Instrument: 210 x 353 x 600 mm (8.3” x 13.9” x 23.6”)
Transport case: 265 x 460 x 750 mm (10.4” x 18.1” x 29.5”).
Weight 13 kg (29 lbs) 21.4 kg (47 lbs) with transport case.
Storage temperature -40°C to +70°C (-40°F to +158°F).

https://www.jpnpartsale.com/refund_returns/