Megger TXL870 Extra Battery Load Unit
$4600,00
Megger TXL870 Extra Battery Load Unit For Torkel | Available EU-USA-AU-ASIA Stock for Low Tax and Free Shipping.
Description
Megger TXL870 Extra Battery Load Unit For Torkel.
The Megger TXL870 Extra Battery Load Unit is designed for use together with TORKEL battery testers. Their purpose is to provide higher load currents for use in constant current or constant power tests. Together, TORKEL and the TXL extra loads form a system that can discharge batteries with currents of up to several kA. TXL extra loads are connected directly to the battery, and TORKEL measures the total current using a clamp-on ammeter.
The Megger TXL870 extra load unit is shut down automatically when TORKEL is stopped.
There are five extra loads available: TXL830, TXL850, TXL865, TXL870, and TXL890. The details for these can be found in the TORKEL data sheet.
| AC/DC Voltage | ||||
|---|---|---|---|---|
| Voltage DC Max | Current Max | Power Max | ||
| TXL830 | 28 V | 300 A | 8.3 kW | |
| TXL850 | 56 V | 300 A | 16.4 kW | |
| TXL870 | 280 V | 112 A | 15.8 kW | |
| TXL890 | 480 V | 62 A | 15.4 kW | |
| Internal Resistance, 3-Position Selector | ||||
| Position 1 | Position 2 | Position 3 | ||
| TXL830 | 0.275 Ω | 0.318 Ω | 0.092 Ω | |
| TXL850 | 0.55 Ω | 0.275 Ω | 0.184 Ω | |
| TXL870 | 4.95 Ω | 2.48 Ω | 1.24 Ω | |
| TXL890 | 14.10 Ω | 7.05 Ω | 3.52 Ω | |
| Maximal Currents, 3 Position Selector | ||||
| Position 1 | Current | Voltage | Cells | Cell Voltage |
| TXL830 | 100 A | 27.6 V | 12 | 2.3 V |
| 78.5 A | 21.6 V | 12 | 1.8 V | |
| TXL850 | 100 A | 55.2 V | 24 | 2.3 V |
| 78.5 A | 43.2 V | 24 | 1.8 V | |
| TXL870 | 50.1 A | 248.4 V | 108 | 2.3 V |
| 39.2 A | 194.4 V | 108 | 1.8 V | |
| TXL890 | 32.3 A | 469.2 V | 204 | 2.3 V |
| 26.0 A | 367.2 V | 204 | 1.8 V | |
| Position 2 | Current | Voltage | Cells | Cell Voltage |
| TXL830 | 200 A | 27.6 V | 12 | 2.3 V |
| 156 A | 21.6 V | 12 | 1.8 V | |
| TXL850 | 200 A | 55.2 V | 24 | 2.3 V |
| 156 A | 43.2 V | 24 | 1.8 V | |
| TXL870 | 50.1 A | 124.2 V | 54 | 2.3 V |
| 39.2 A | 97.2 V | 54 | 1.8 V | |
| TXL890 | 35.2 A | 248.4 V | 108 | 2.3 V |
| 27.8 A | 194.4 V | 108 | 1.8 V | |
| Position 3 | Current | Voltage | Cells | Cell Voltage |
| TXL830 | 300 A | 27.6 V | 12 | 2.3 V |
| 235 A | 21.6 V | 12 | 1.8 V | |
| TXL850 | 300 A | 55.2 V | 24 | 2.3 V |
| 235 A | 43.2 V | 24 | 1.8 V | |
| TXL870 | 100 A | 124.2 V | 54 | 2.3 V |
| 74.8 A | 97.2 V | 54 | 1.8 V | |
| TXL890 | 70.5 A | 248.4 V | 108 | 2.3 V |
| 55.2 A | 194.4 V | 108 | 1.8 V | |
| Environment | The instrument is intended for use in high voltage substations and industrial environments. | |||
| Operating temperature | 0°C to +40°C (32°F to +104°F). | |||
| Storage temperature | -40°C to +70°C (-40°F to +158°F). | |||
| CE Marking | LVD: IEC61010-1:2010 EMC: IEC61326 -1. |
|||
| Main Voltage | 100 – 240 V AC, 50 / 60 Hz. | |||
| Power consumption | 75 W (max). | |||
| Protection | Thermal cut-outs, automatic overload protection. | |||
| Dimensions | Instrument: 210 x 353 x 600 mm (8.3” x 13.9” x 23.6”) Transport case: 265 x 460 x 750 mm (10.4” x 18.1” x 29.5”). |
|||
| Weight | 13 kg (29 lbs) 21.4 kg (47 lbs) with transport case. | |||
| Storage temperature | -40°C to +70°C (-40°F to +158°F). | |||







Reviews